Resumen
Fast and precise tracking of grid voltage attributes is essential for the smooth and reliable control and operation of grid-side converters. The synchronous reference-frame phase-locked loop (SRF-PLL) approach is commonly used for this purpose, although it has issues related to the stability limit and sluggish transient response. Consequently, PLL-less grid synchronization approaches are becoming increasingly prevalent. In this context, in the present paper, a discrete Fourier transform-based band pass filter (DFT-BPF) is designed in the prefiltering stage for the purpose of extracting the fundamental frequency positive sequence component (FFPS) from unbalanced and distorted grid conditions. Despite being widely used, the SRF-PLL is struggling with stability issues and demands tedious tuning effort. For this objective, a simple frequency estimator has been developed, which is capable of accurately estimating the fundamental frequency. Additionally, a curve fitting based error correction technique is employed to adaptively estimate the amplitude and phase-angle of the fundamental component without using frequency feedback loop. The experimental results validate the efficacy of the proposed scheme.
| Idioma original | Inglés |
|---|---|
| Número de artículo | 108926 |
| Publicación | International Journal of Electrical Power and Energy Systems |
| Volumen | 148 |
| DOI | |
| Estado | Publicada - jun. 2023 |
| Publicado de forma externa | Sí |
Nota bibliográfica
Publisher Copyright:© 2022 Elsevier Ltd
Huella
Profundice en los temas de investigación de 'Enhanced PLL-less grid synchronization algorithm amidst unbalanced and distorted three-phase grid conditions'. En conjunto forman una huella única.Citar esto
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver