Abstract
This work presents a case study of a modular photovoltaic (PV) plant where PV panel arrays are connected to the grid through cascaded single-phase current-source inverters. It is shown that, under non-uniform insolation conditions of the PV arrays, the output voltages of the cascaded inverters become unbalanced. Therefore, a dc voltage elimination control loop is proposed to balance the output voltage of the H bridges. Additionally a control technique called virtual synchronous generator (VSG) is applied to the PV plant in order to support the control of the grid frequency emulating an inertial response and providing damping and droop power. For the simulated cases the PV plant was always capable of performing the VSG functions, in spite of the unbalance condition of the output voltages of the H bridges. However, when the proposed dc voltage elimination control loop was in operation the maximum peak output voltage and the amplitude of its fundamental component were reduced in 13.3 % and 27 % respectively.
| Original language | English |
|---|---|
| Title of host publication | IECON Proceedings (Industrial Electronics Conference) |
| Publisher | Institute of Electrical and Electronics Engineers Inc. |
| Pages | 5565-5570 |
| Number of pages | 6 |
| ISBN (Electronic) | 9781479940325 |
| DOIs | |
| State | Published - 24 Feb 2014 |
| Externally published | Yes |
Publication series
| Name | IECON Proceedings (Industrial Electronics Conference) |
|---|
Bibliographical note
Publisher Copyright:© 2014 IEEE.
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Fingerprint
Dive into the research topics of 'On the control of a grid-connected photovoltaic plant under non-uniform insolation'. Together they form a unique fingerprint.Cite this